Mv Medium Voltage ABC Cable Power Cable

  • Description
Product Detail

    APPLICATION:
    Medium voltage Aerial bundled cables are mainly used for secondary overhead lines on poles or as feeders to residential premises.
    STANDARDS
    Basic design to IEC 60502 / AS/NZS 3599-1 standards
    CABLE CONSTRUCTION
    Phase Conductor: Circular compacted stranded H68 aluminium to BS2627.
    Conductor Screen: Extruded semi-conductive layer.
    insulation: XLPE.
    insulation Screen: Extruded semi-conductive layer.
    metallic Screen(optional): Copper wire screen or copper tape screen.
    Separator: Semi-conductive swellable tape.
    outer Sheath: HDPE.
    Support Conductor: Galvanized steel wires.
    Assembly: Three XLPE insulated screened cores are bundled around the galvanized steel  wires in a right hand lay.
    Construction Parameters
    IEC 60502 6.35/11 kV ABC for Overhead Distribution Lines



    Number of Cores
    xNominal
    Cross Section
    Phase ConductorMessenger Suspension UnitContinuous
    current
    rating
    at
    300C 
    ambient
    temp
    StrandingNominal
    Sectional
    Area
    Maximum
    Conductor
    Resistance
    StrandingNominal
    Sectional
    Area
    Breaking
    Load
    No.×mm²No.×mmmm²O/KmNo.×mmmm²KN A
    3X50 + 1X2519/1.78500.6417/3.05060116
    3X70 + 1X5019/.14700.4437/3.155062210
    3X95+ 1X5019/2.52950.327/3.05060173
    3X185+1X12037/2.521850.1647/4.67120150259
    3X150 +1X5037/2.251500.2067/3.155062365
    3X240 +1X5061/2.252400.1257/3.155062500


     Other cross-sections can be offered upon request.
    IEC 60502 19/33 kV ABC for Overhead Distribution Lines


    Number of Cores
    xNominal
    Cross Section
    Phase ConductorMessenger Suspension UnitContinuous
    current
    rating
    at
    300C 
    ambient
    temp
    StrandingNominal
    Sectional
    Area
    Maximum
    Conductor
    Resistance
    StrandingNominal
    Sectional
    Area
    Breaking
    Load
    No.×mm²No.×mmmm²O/KmNo.×mmmm²KN A
    3X50 + 1X5019/1.78500.6417/3.05060165
    3X150+ 1X5037/2.251500.2067/3.05060315
    3X185+1X7037/2.521850.1647/3.577091355
    3X70 +1X5019/2.1470.4437/3.155062250
    3X150 +1X5037/2.251500.2067/3.155062370


     Other cross-sections can be offered upon request.
    AS/NZS 3599 Part 1 6.35/11 kV AL/XLPE /HDPE Non-screened Cables


    Number of Cores
    xNominal
    Cross Section
    Phase ConductorMessenger
    Suspension Unit
    Nominal Sectional AreaBreaking
    Load
    Diameter
    of
    Conductor
    Thickness
    of
    Insulation
    Thickness
    of
    Insulation
    Screen
    Thickness
    of
    Sheath
    Stranding
    No.×mm²mmmmmmmmNo.×mmmm²KN
    3x356.93.40.81.27/4.7552.41370
    3x508.13.40.81.27/4.7554.61530
    3x709.73.40.81.27/4.7557.81790
    3x9511.43.40.81.27/4.7561.32100
    3x12012.83.40.81.219/3.5067.32540
    3x15014.23.40.81.219/3.5070.12840
    3x18515.73.40.81.219/3.5073.13190


    Other cross-sections can be offered upon request.
    AS/NZS 3599 Part 1 6.35/11 kV AL/XLPE /CWS/HDPE Screened Cables


    Number of Cores
    xNominal
    Cross Section
    Diameter
    of
    Conductor
    Thickness
    of
    Insulation
    Thickness
    of
    Insulation Screen
    Copper Wire Screen
    Stranding
    Thickness
    of
    Sheath
    Galvanized Steel Wire StrandingNominal Sectional AreaBreaking
    Load
    No.×mm²mmmmmmNo.×mmmmNo.×mmmm²KN
    Light Duty Screen
    3x356.93.40.825/0.851.87/2.0054.11820
    3x356.93.40.825/0.851.819/2.0058.12130
    3x508.13.40.825/0.851.819/2.0060.42300
    3x709.73.40.825/0.851.819/2.0063.62570
    3x9511.43.40.825/0.851.819/2.0067.02900
    3x12012.83.40.825/0.851.819/2.0069.83190
    3x15014.23.40.825/0.851.919/2.0073.03530
    3x18515.73.40.825/0.851.919/2.0076.03890
    Heavy Duty Screen
    3x356.93.40.840/0.851.87/2.0054.12050
    3x356.93.40.840/0.851.819/2.0058.12360
    3x508.13.40.823/1.351.819/2.0062.42820
    3x709.73.40.832/1.351.819/2.0065.63440
    3x9511.43.40.839/1.351.819/2.0069.04030
    3x12012.83.40.839/1.351.819/2.0071.84320
    3x15014.23.40.839/1.351.919/2.0075.04670
    3x18515.73.40.839/1.351.919/2.0078.05020


     Other cross-sections can be offered upon request.
    AS/NZS 3599 Part 1 12.7/22 kV AL/XLPE /HDPE Non-screened Cables

    Number of Cores
    xNominal
    Cross Section
    Phase ConductorMessenger
    Suspension Unit
    Nominal Sectional AreaBreaking
    Load
    Diameter
    of
    Conductor
    Thickness
    of
    Insulation
    Thickness
    of
    Insulation
    Screen
    Thickness
    of
    Sheath
    Stranding
    No.×mm²mmmmmmmmNo.×mmmm²KN
    3x356.95.50.81.27/4.7561.01780
    3x508.15.50.81.27/4.7563.31970
    3x709.75.50.81.27/4.7566.52260
    3x9511.45.50.81.27/4.7569.92600
    3x12012.85.50.81.219/3.5075.93070
    3x15014.25.50.81.219/3.5078.73390
    3x18515.75.50.81.219/3.5081.73760


     Other cross-sections can be offered upon request.
    AS/NZS 3599 Part 1 12.7/22 kV AL/XLPE /CWS/HDPE Screened Cables

    Number of Cores
    xNominal
    Cross Section
    Diameter
    of
    Conductor
    Thickness
    of
    Insulation
    Thickness
    of
    Insulation Screen
    Copper Wire
    Screen Stranding
    Thickness
    of
    Sheath
    Galvanized
    Steel Wire Stranding
    Nominal Sectional
    Area
    Breaking
    Load
    No.×mm²mmmmmmNo.×mmmmNo.×mmmm²KN
    Light Duty Screen
    3x356.95.50.825/0.851.87/2.0062.72280
    3x356.95.50.825/0.851.819/2.0066.72580
    3x508.15.50.825/0.851.819/2.0069.02780
    3x709.75.50.825/0.851.919/2.0072.63110
    3x9511.45.50.825/0.851.919/2.0076.03460
    3x12012.85.50.825/0.852.019/2.0079.23810
    3x15014.25.51.025/0.852.019/2.0082.84230
    3x18515.75.51.025/0.852.119/2.0086.24650
    Heavy Duty Screen
    3x356.95.50.840/0.851.87/2.0062.72510
    3x356.95.50.840/0.851.819/2.0066.72810
    3x508.15.50.823/1.351.819/2.0071.03300
    3x709.75.50.832/1.351.919/2.0074.63970
    3x9511.45.50.839/1.351.919/2.0078.04600
    3x12012.85.50.839/1.352.019/2.0081.24950
    3x15014.25.51.039/1.352.019/2.0084.85360
    3x18515.75.51.039/1.352.119/2.0088.25790


    Other cross-sections can be offered upon request.
    Technical Data

    Nominal
    Cross Section
    Continuous Current Rating
    Still air1m/s wind2m/s wind
    mm²AAA
    35105145165
    50125170200
    70150215250
    95180260300
    120205300350
    150230340395
    185265390450


    Packaging & Shipping


    Mv  Medium VoltageABC Cable power cable


    1) Packing length:100 to 1,000m reeled in carton drum 
    2) Outer packing: wooden case, carton box
    3) Other packing requirement according to client's request.


    Our Services




    Mv  Medium VoltageABC Cable power cable


    Advanced connectors & assembly cables machines and testing equipments.
    Large production capacity, short delivery.
    Prompt quotation for your inquiry.
    More than 10 years experiences in cable and wire field.

    OEM/ODM service available, help you on designing.

    Strict QC checking before delivery.
    Professional connector and cable manufacturer, with good quality and competitive price.
    free samples are available for further evaluation and you are highly welcome to visit our factory anytime!!


Send your message to this supplier
To:  

Huatong Cable Inc

* Content:  

For better quotations, include:

- A self introduction

- Special requests, if any

Quantity:  

  
Not exactly what you want? One request, multiple quotations Get Quotations Now >>